Double Check Valve
   HOME

TheInfoList



OR:

A double check valve or double check assembly (DCA) is a
backflow prevention device A backflow prevention device is used to protect potable water supplies from contamination or pollution due to backflow. In water distribution systems, water is normally maintained at a significant pressure to enable water to flow from the tap, s ...
designed to protect water supplies from
contamination Contamination is the presence of a constituent, impurity, or some other undesirable element that spoils, corrupts, infects, makes unfit, or makes inferior a material, physical body, natural environment, workplace, etc. Types of contamination ...
. It is different from the two-way check valves (sometimes erroneously referred to as double check valves) used in air brake systems on heavy trucks which select from the highest pressure source. It consists of two
check valve A check valve, non-return valve, reflux valve, retention valve, foot valve, or one-way valve is a valve that normally allows fluid ( liquid or gas) to flow through it in only one direction. Check valves are two-port valves, meaning they have ...
s assembled in series.Double Check Detector Assembly article, portlandoregon.gov
/ref> This employs two operating principles: firstly one check valve will still act, even if the other is jammed wide open. Secondly the closure of one valve reduces the pressure differential across the other, allowing a more reliable seal and avoiding even minor leakage. Small valves may be so compact as to be barely noticeable particularly when they are integrated into the bodies of existing taps (faucets). Larger check valves may be installed with ball valves at the ends, for isolation and testing. Often, test cocks (very small ball valves) are in place to attach test equipment for evaluating whether the double check assembly is still functional. The double check valve assembly is suitable for prevention of back pressure and back siphonage, but is not suitable for high hazard applications. It is commonly used on lawn
irrigation Irrigation (also referred to as watering) is the practice of applying controlled amounts of water to land to help grow crops, landscape plants, and lawns. Irrigation has been a key aspect of agriculture for over 5,000 years and has been devel ...
,
fire sprinkler A fire sprinkler or sprinkler head is the component of a fire sprinkler system that discharges water when the effects of a fire have been detected, such as when a predetermined temperature has been exceeded. Fire sprinklers are extensively use ...
and
combi-boiler Water heating is a heat transfer process that uses an energy source to heat water above its initial temperature. Typical domestic uses of hot water include cooking, cleaning, bathing, and space heating. In industry, hot water and water heated t ...
systems. If the hazard is higher, even a relatively low hazard such as using antifreeze in the fire sprinkler system, then a more reliable check valve such as a reduced pressure zone device may be mandated.


Dual Check Valve

A dual check backflow preventer is similar to a double check valve in operation. It has two independent spring-loaded check valves. However, dual check valves usually do not include shutoff valves, may or may not be equipped with test cocks or ports and is generally less reliable than a double check valve.


See also

* Air gap * Hydrostatic loop * Pressure vacuum breaker * Chemigation valve *
Reduced pressure principle BFP A reduced pressure zone device (RPZD, RPZ, or RPZ valve) is a type of backflow prevention device used to protect water supplies from contamination. RPZDs may also be known as reduced pressure principle (RP), reduced pressure principle backflow p ...
* Atmospheric vacuum breaker * Reduced pressure zone device * Air brake (road vehicle)


References

Plumbing valves Irrigation Backflow {{civil-engineering-stub